Short answer. A guard on a Direct on Line (DOL) starter has to settle two questions before the contactor coil may pull in: is every one of the three incoming conductors live, and do those voltages arrive in the right rotational order. The circuit circulated as a Design Ideas Submission Guide entry settles both with small-signal parts — rectified phase voltages, Schmidt trigger inverters, two flip-flops for order, an OR gate into a retriggerable monostable for presence — and holds Relay RL1 energized only when both checks pass. Put its contact in the starter's stop path and a bad supply trips the machine instead of slowly cooking a winding.
Begin the review at the terminal block, not at the motor. On a pump or compressor skid a phase seldom dies in a clean, documented way: it dies as a fuse holder that lost spring pressure, a crimp that crept loose during a panel retrofit, or two conductors swapped by a contractor in a hurry. The machine keeps running on two phases, the surviving windings take the current, and the first honest signal is hot varnish in the electrical room.
The design covers two fault classes, phase loss and wrong sequence; overvoltage, undervoltage and unbalance are not in the logic, and confusing them is the most common specification error on small machine builds.
This board earns its place where sequence and loss are the exposure: retrofits, motor swaps, skids that move between buildings. Where the supply quality itself is the history, buy the unbalance function.
Each leg of a star-connected three-phase transformer feeds one rectifier, D1, D2, D3, and each rectified phase voltage drives a transistor, Q1, Q2, Q3. Those collectors deliver square waves that U1 Schmidt trigger inverters sharpen, so downstream logic never guesses at a slow zero crossing.

Figure 1: a single common transformer also generates the 5 V DC rail used by every logic element in this phase sequence-and-failure circuit.
U1C sets flip-flop U5A when the R phase is the first edge in; the Y phase resets U5A through U1A. The Q output of U5A feeds the D input of flip-flop U5B, and the B phase — last in the assumed order — clocks that D value into the output. Correct order (R-Y-B) leaves the Q output of U5B LOW; reverse it, for example R-B-Y, and the same output goes HIGH. In a new design this is a handful of LUT cells; on a maintenance bench it is two packages you can probe one-handed.
U1A, U1B and U1C feed OR gate U2A. With R, Y and B healthy, U2A holds HIGH, the retriggerable monostable U3A sees plain DC, and its output stays LOW. Open any phase and U2A becomes a pulse train, each pulse rearming U3A and pinning its output HIGH. With the RC values shown the monostable pulse width is approximately 12 msec — a couple of half-cycles at 50 Hz, tight enough to act fast, loose enough to reject one contact bounce.
LOW at both detector outputs means the supply is in order: U2B pulls LOW, Q1 saturates, Relay RL1 energizes. Its contact belongs in series with the OFF button of the motor starter, so the relay dropping out trips the motor. Power and ground pins are omitted from Figure 1 and must be tied to VDD and VSS. The 5 V the logic needs comes from the same three-phase transformer through a LM7805 regulator; line enters at terminal block J1 and relay outputs leave at J2. Assemble the board unchanged in countries such as India, which runs 230 V, 50 Hz service; for the United States, re-specify the transformer as 110 V/5 V at 60 Hz and keep the published parts list.
| Dimension | Discrete logic build | Packaged phase monitoring relay |
|---|---|---|
| Faults detected | Sequence and phase loss | Adds unbalance, over- and undervoltage, restart delay, fault memory |
| Input range | Set by the transformer winding | Catalogue types cover 208–480 VAC systems |
| Panel footprint | Board plus magnetics | 22.5 mm DIN module or 8-pin plug-in relay with 10 A output |
| Troubleshooting | Probe points at each gate | Normal and trip LEDs, whole-unit swap |
| Lead-time exposure | Custom transformer dominates | Multi-maker commodity stock |
The honest comparison is with devices such as the Omron K8DS-PM family, the Macromatic PMPU-FA8X plug-in units (208–480 VAC, 10 A SPDT/SPNO output) and Gavazzi's 22.5 mm three-phase monitors, all of which add unbalance and voltage bands that this circuit does not attempt. The discrete build wins on three narrow grounds: a voltage or reference arrangement nobody stocks, a spare-parts culture that already stocks small-signal logic and relays, and a chip-count discipline of the kind we looked at when replacing a comparator with an AND gate in a ripple divider. Where a packaged unit is chosen, its adjustment dials are the weakest mechanical link — our potentiometer comparison by function, duty cycle, accuracy and environment is the checklist to run before trusting a set threshold for years.
No. U2A only asks whether pulses exist, so partial asymmetry passes. If unbalance is the site problem, specify a monitor with an adjustable unbalance threshold and keep the NEMA MG-1 1% figure as the alarm point.
A logic-level output can drive a coil-side interlock directly and legally; switching a motor's power path from a board would need contactors, ratings and arc management that this design deliberately avoids.
At 60 Hz it covers more line cycles, which is harmless. At 400 Hz service, common on rotating amplifiers and some aerospace benches, 12 msec spans several cycles and the RC should be recomputed — another reason the magnetics, not the gates, is the part to re-specify per site.
Supply pins and decoupling, then the rectified leg amplitudes. Because Figure 1 omits VDD and VSS, an unwired supply pin is the most frequent cause of intermittent drop-out.
Do not price this monitor against the component list. Price it against a rewinding order, a compressor swap, or a line stopped while a technician hunts a phase. The investment decision is boring and specific: dual-source the transformer, because windings are the long lead item and the one that changes between 230 V, 50 Hz and 60 Hz service; keep small-signal transistors, Schmidt inverters, flip-flops and a relay in the bin, because those stocks are deep and cheap; and standardise on one protection architecture per plant so the commissioning steps above are done once and repeated, not reinvented on every retrofit. Capacity plans fail on the single-source item nobody re-quoted, not on the four-rupee logic gate.