Short answer. A guard on a Direct on Line (DOL) starter has to settle two questions before the contactor coil may pull in: is every one of the three incoming conductors live, and do those voltages arrive in the right rotational order. The circuit circulated as a Design Ideas Submission Guide entry settles both with small-signal parts — rectified phase voltages, Schmidt trigger inverters, two flip-flops for order, an OR gate into a retriggerable monostable for presence — and holds Relay RL1 energized only when both checks pass. Put its contact in the starter's stop path and a bad supply trips the machine instead of slowly cooking a winding.

Begin the review at the terminal block, not at the motor. On a pump or compressor skid a phase seldom dies in a clean, documented way: it dies as a fuse holder that lost spring pressure, a crimp that crept loose during a panel retrofit, or two conductors swapped by a contractor in a hurry. The machine keeps running on two phases, the surviving windings take the current, and the first honest signal is hot varnish in the electrical room.

What this monitor catches, and what it deliberately ignores

The design covers two fault classes, phase loss and wrong sequence; overvoltage, undervoltage and unbalance are not in the logic, and confusing them is the most common specification error on small machine builds.

  • Loss is fast. Under primary single-phasing the current in one remaining phase climbs to roughly 230% of normal, per Eaton's Bussmann motor-protection application library — and a thermal overload block on a motor running at 70% of nameplate current can ride through that.
  • Unbalance is slow and hidden. NEMA MG-1 (clause 14.35) puts the practical operating ceiling at 1% voltage unbalance, because 1% voltage asymmetry typically produces 6–10% current asymmetry at the terminals.
  • The machine standard frames the normal window. IEC 60204-1 clause 4.3.2 assumes steady-state supply between 0.9 and 1.1 of nominal voltage and keeps the negative-sequence component of a three-phase supply within 2% of the positive-sequence value — sensible reference points when setting any threshold.

This board earns its place where sequence and loss are the exposure: retrofits, motor swaps, skids that move between buildings. Where the supply quality itself is the history, buy the unbalance function.

The signal path, device by device

Each leg of a star-connected three-phase transformer feeds one rectifier, D1, D2, D3, and each rectified phase voltage drives a transistor, Q1, Q2, Q3. Those collectors deliver square waves that U1 Schmidt trigger inverters sharpen, so downstream logic never guesses at a slow zero crossing.

The reference schematic

Figure 1: a single common transformer also generates the 5 V DC rail used by every logic element in this phase sequence-and-failure circuit.

Sequence: two flip-flops and one timing assumption

U1C sets flip-flop U5A when the R phase is the first edge in; the Y phase resets U5A through U1A. The Q output of U5A feeds the D input of flip-flop U5B, and the B phase — last in the assumed order — clocks that D value into the output. Correct order (R-Y-B) leaves the Q output of U5B LOW; reverse it, for example R-B-Y, and the same output goes HIGH. In a new design this is a handful of LUT cells; on a maintenance bench it is two packages you can probe one-handed.

Presence: an OR gate and a 12 msec retrigger

U1A, U1B and U1C feed OR gate U2A. With R, Y and B healthy, U2A holds HIGH, the retriggerable monostable U3A sees plain DC, and its output stays LOW. Open any phase and U2A becomes a pulse train, each pulse rearming U3A and pinning its output HIGH. With the RC values shown the monostable pulse width is approximately 12 msec — a couple of half-cycles at 50 Hz, tight enough to act fast, loose enough to reject one contact bounce.

Output stage, logic rail and the one part that changes by country

LOW at both detector outputs means the supply is in order: U2B pulls LOW, Q1 saturates, Relay RL1 energizes. Its contact belongs in series with the OFF button of the motor starter, so the relay dropping out trips the motor. Power and ground pins are omitted from Figure 1 and must be tied to VDD and VSS. The 5 V the logic needs comes from the same three-phase transformer through a LM7805 regulator; line enters at terminal block J1 and relay outputs leave at J2. Assemble the board unchanged in countries such as India, which runs 230 V, 50 Hz service; for the United States, re-specify the transformer as 110 V/5 V at 60 Hz and keep the published parts list.

Commissioning sequence: seven steps from bench to line

  1. Energize the transformer alone and confirm each rectified leg on a scope before the logic is in circuit.
  2. Bond VDD and VSS on every package — the drawing omits them, and a floating supply pin reads as a ghost fault.
  3. Inspect the three square waves at U1 for amplitude, edge symmetry and equal phase-to-phase spacing.
  4. Sequence test with power off: swap two incoming conductors at J1, energize, and confirm RL1 stays dropped.
  5. Loss test with the motor disconnected: open one phase at J1 and time the drop-out; the 12 msec window sets the floor.
  6. Interlock test with the starter live: prove the contact interrupts the coil through the stop chain and not through some feed that survives the fault.
  7. Reset policy in writing: decide whether the machine may re-energize when a fault clears. Packaged phase monitors usually do so automatically after a restart delay, and this circuit likewise releases as soon as U2A goes quiet — so where an operator can be inside the guard, add a manual reset and align the stop chain with the stop categories of IEC 60204-1.

Board-level build or catalogue module: what decides it

DimensionDiscrete logic buildPackaged phase monitoring relay
Faults detectedSequence and phase lossAdds unbalance, over- and undervoltage, restart delay, fault memory
Input rangeSet by the transformer windingCatalogue types cover 208–480 VAC systems
Panel footprintBoard plus magnetics22.5 mm DIN module or 8-pin plug-in relay with 10 A output
TroubleshootingProbe points at each gateNormal and trip LEDs, whole-unit swap
Lead-time exposureCustom transformer dominatesMulti-maker commodity stock

The honest comparison is with devices such as the Omron K8DS-PM family, the Macromatic PMPU-FA8X plug-in units (208–480 VAC, 10 A SPDT/SPNO output) and Gavazzi's 22.5 mm three-phase monitors, all of which add unbalance and voltage bands that this circuit does not attempt. The discrete build wins on three narrow grounds: a voltage or reference arrangement nobody stocks, a spare-parts culture that already stocks small-signal logic and relays, and a chip-count discipline of the kind we looked at when replacing a comparator with an AND gate in a ripple divider. Where a packaged unit is chosen, its adjustment dials are the weakest mechanical link — our potentiometer comparison by function, duty cycle, accuracy and environment is the checklist to run before trusting a set threshold for years.

Four mistakes that turn protection into decoration

  • Trusting the thermal overload to see single phasing. It is sized for sustained overcurrent, not for a phase that vanished upstream while the load stayed light.
  • Reading a closed contact as a healthy supply. The presence gate answers per phase; a conductor that is present but deeply sagging still reads normal.
  • Copying the transformer onto a 3-wire delta without re-deriving it. In our reading of the schematic each rectified leg is referenced to the star point, so a system without that reference needs a different winding connection and turns ratio — treat this as analysis, not as a published feature.
  • Ignoring the regulator's headroom. A LM7805 needs input margin above its 5 V output; check dropout and dissipation at the bottom of the supply range before blaming the logic for resets.

FAQ: three-phase monitoring in practice

Can this circuit detect phase unbalance?

No. U2A only asks whether pulses exist, so partial asymmetry passes. If unbalance is the site problem, specify a monitor with an adjustable unbalance threshold and keep the NEMA MG-1 1% figure as the alarm point.

Why interrupt the stop chain instead of the power circuit?

A logic-level output can drive a coil-side interlock directly and legally; switching a motor's power path from a board would need contactors, ratings and arc management that this design deliberately avoids.

Does the 12 msec window still fit a 60 Hz or 400 Hz installation?

At 60 Hz it covers more line cycles, which is harmless. At 400 Hz service, common on rotating amplifiers and some aerospace benches, 12 msec spans several cycles and the RC should be recomputed — another reason the magnetics, not the gates, is the part to re-specify per site.

RL1 chatters on an otherwise healthy line. Where do I look first?

Supply pins and decoupling, then the rectified leg amplitudes. Because Figure 1 omits VDD and VSS, an unwired supply pin is the most frequent cause of intermittent drop-out.

Where the money and the capacity actually move

Do not price this monitor against the component list. Price it against a rewinding order, a compressor swap, or a line stopped while a technician hunts a phase. The investment decision is boring and specific: dual-source the transformer, because windings are the long lead item and the one that changes between 230 V, 50 Hz and 60 Hz service; keep small-signal transistors, Schmidt inverters, flip-flops and a relay in the bin, because those stocks are deep and cheap; and standardise on one protection architecture per plant so the commissioning steps above are done once and repeated, not reinvented on every retrofit. Capacity plans fail on the single-source item nobody re-quoted, not on the four-rupee logic gate.

References

  • Eaton (Bussmann) — Motor protection: voltage unbalance and single-phasing: application library PDF
  • ACHR News — NEMA MG-1 limits and the 1% voltage unbalance rule: article
  • Machinery Safety 101 — IEC 60204-1 clause 4.3.2 supply envelope: note
  • AutomationDirect — phase monitor relay specification, reset behaviour: specification PDF
  • Omron — K8DS-PM three-phase voltage and phase-sequence/phase-loss relay: datasheet
  • Gavazzi — three-phase monitors in 22.5 mm housings up to 480 V: product page
  • Amphenol Connect — Macromatic PMPU-FA8X three-phase monitor relay: product overview